TVLK with LABCONTROL-ANALOGUE (0-10V communication system)
The main area of application of the TVLK is laboratory ventilation. It is used for the variable volume flow control on fume hoods. Because the exhaust from fume hoods can contain a wide range of aggressive substances, the TVLK consists of highly resistant material.
The connection diameter is 250 mm, which fits the standard connection of most fume hoods. In laboratory environments, many installations must be accommodated in the ceiling. For this reason, the installation length is limited to only 400 mm. The devices's functionality was optimised for this installation length and its resistance to unfavourable upstream conditions allows the TVLK to be installed directly on the fume cupboard.
Technical data TVLK
- Round connections Ø 250 mm on both sides
- Can be supplied with flange and counterflange on request
- Total length only 400 mm
- All parts in contact with exhaust air are made of polypropylene PPs
- Resistant against unfavourable currents
- Full air-tight shut-off as per DIN EN1751
- Differential pressure range: 80 to 1000 Pa
- Volume flow range 90 - 2214 m³/h
- Supply voltage 24 V AC or 230 V AC, depending on control component
- Connected load 25 VA
- Protection type IP 20
TVLK certificates according to DIN EN 1475 part 6
The TVLK can be combined with the LABCONTROL-ANALOGUE system (TCU-II controller) as follows:
TVLK with control component TRA
- Supply voltage 24 V AC
- Standard operating unit and optional extended operating unit AF-1
TVLK with control component TUA
- Supply voltage 230 V AC
- Extended operating unit AF-1
TVLK with control component TR0
- Supply voltage 24 V AC
- Standard operating unit or optional extended operating unit AF-1
- Without damper drive
- With analogue output 0-10 V for control of variable speed drive (VSD) / fan
| Downloads |
Group |
Type |
Ident-No. |
Type / Size |
| |
|
|
|
|
| Design changes of plastic flanges |
VARYCONTROL |
Technical Information |
PG 2001 |
PDF / 181 KB |
| TCU-II |
LABCONTROL-ANALOG |
Technical Information |
PI/7.4/1/D/1 |
PDF / 2.5 MB |
Laboratory System Management
Overview brochures
The LABCONTROL system - An introduction into system characteristics, components and typical application areas
Installation examples
Tailor-made solutions
the air management system LABCONTROL
More ...
Contact
TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel: +49 (0)2845 / 202-0
Contact and locations